To set up and scale the DELos SI pressure transmitter for accurate level measurement in a tank.
Allen key or screwdriver (0.5 × 3 mm)
Power supply to transmitter
Process tank with liquid
Ensure transmitter is properly mounted and no leakage is present.
Perform calibration only when process is stable.
Default code = 0072
Unscrew the protective screw.
Insert tool in the programming slot.
Press until the 3rd digit from left blinks and display turns red.
Rotate and set value to 7.
Press until the 4th digit blinks.
Rotate and set value to 2.
Press once to enter parameter mode.
Rotate until Uni.P appears.
Press once.
Select mbar.
Press once to confirm.
Rotate until Dam.P appears.
Press once.
Set value to 1.0 s.
Press once to confirm.
Rotate until S.TyP appears.
Press once.
Select 4.20A (4–20 mA).
Press once to confirm.
Press and hold for >3 seconds to return to measurement mode.
Fill tank until just the diaphragm is covered.
Wait until reading is stable.
Note the pressure value displayed.
Fill tank to maximum required level.
Wait until reading is stable.
Note the pressure value displayed.
Press once to enter parameter mode.
Rotate until Sc.Lo appears.
Press once.
Enter low-level pressure value.
Press once to confirm.
Rotate until Sc.Hi appears.
Press once.
Enter high-level pressure value.
Press once to confirm.
Verify:
4 mA = Low level
20 mA = High level
Check few intermediate levels.
Fluctuating reading → increase damping.
Wrong level mapping → recheck Sc.Lo and Sc.Hi.
No output change → check loop wiring and S.TyP.